- Loops: 1 (DMTech protocol)
- Devices per loop: 250
- The maximum resistance of the loop – 100 Ohm
- Maximum loop consumption – 500 mA
- Connecting line – with two-wire shield
- Conventional line 1: (up to 32 conventional fire detectors)
- Zones: 8
- Solution: 2
- Output ports (non-monitoring, programmable, relay type): 3
- Output under fault conditions (relay type, C/NC/NO): 1
- Memory capacity: 1024 data
- Screen: 4*20 characters LCD
- Multilingual support: has
- Programming: DMTech Software
- Standard: EN54 – 2/4
- Interfaces for communication with external devices – RS485 and USB.
- Backup power supply – 2 x 12V DC / capacity C20 (4.5 or 5)Ah
- Electrical output: (24±3.6)V / 2А
- Main power supply: 90 ÷ 264 VAC / 50 ÷ 60 Hz
- Operating temperature: -10°C to +40°C
- Dimensions: 305 x 250 x 95 mm
- Weight: (without battery) 1.2 kg
Certificate PDF FILE: 200609_1922-CPR-1267_EN_KM_FP9000A